LX Series Models

LX Series Models
Miura is known world-wide for our commitment to protecting the environment and our innovative and efficient industrial boiler designs. Our low NOx steam and hot water boilers meet and exceed current and proposed regulations for nitrogen oxide emissions levels, as low as 9ppm NOx at 3%, corrected O2. These industrial boilers far exceed any boilers currently on the market.
  • Gas fired: Natural Gas or Propane
  • High and low pressure steam options available (300 MAWP, 170 MAWP or 15 MAWP)
  • Hot water boilers are available depending on models
  • Compact, an LX 200 Boiler can fit through a standard doorway
  • Naturally low NOx (nitrogen oxides) Rating as low as: 9ppm depending on model
LX Series Model Design
The Miura LX Series industrial boiler design consists of rows of vertical tubes sandwiched between two rectangular headers. Both headers are encased in a castable refractory with only the tubes exposed to flame and/or combustion gases. The upper header is attached to the lower header only by the tubes. As the tubes expand and contract, the headers float up and down accordingly.
This ’floating header’ concept greatly reduces stress and allows for the use of cold feedwater without the fear of significant thermal shock. The ’leaky tube’ problems associated with firetube and bent watertube designs have been eliminated.
Low NOx "No Furnace" Boiler
Cool, soft flame wraps around the tubes from a flame spread over a large surface area. This naturally controlled burn results in unbelievably low NOx, compact size and high efficiency.
Full Steam Output In Less Than 5 Minutes
Floating headers mean fast start-up. Miura boilers produce fast steam in less than 5 minutes from a cold start-up. Standard firetubes require 1 to 1.5 hour start-up times. Miura’s unique design yields significant time and fuel savings.
Smaller is Better
Miura’s LX Series boilers occupy 50% less floor space than typical firetubes, and do not require tube pull space. Double your capacity in the same space, or reduce space requirements by half for new construction. Miura’s compact design means much smaller radiation losses and larger fuel savings.
Early Warning Scale Monitor
Scale is a problem all boilers have to deal with. Scale forms when boiler feedwater is not properly treated. Advanced scale formation acts as an insulator; only an eggshell thickness of scale results in a 10% efficiency loss, higher fuel bills and possible damage to the boiler system.
As standard equipment, all Miura LX models are equipped with a thermocouple attached directly to a tube. Should scale begin to form, the MIURA boiler will alert the operator - allowing the operator to trace and repair the source of the water hardness. The scale can be removed to restore the boiler to its original efficiencies - saving tens of thousands of dollars in wasted fuel and repair bills.
Unbeatable In-Service Efficiencies
Miura’s computer-aided design results in optimal heating surface transfer with minimal water content for fuel-to-steam efficiencies of 85%. Typical firetube designs can deliver up to 83% fuel-to-steam efficiencies. However, in actual use, Miura averages 10 to 40% fuel savings over standard firetube designs. How does a 2% difference in fuel-to-steam efficiencies translate into a 10 to 40% ACTUAL FUEL SAVINGS? Contact your local Miura representative for details.
Miura LX Series Steam Boiler
LX(L)-50 SG
LX Gas/Low NOx Series – Low and High Pressure Steam Boiler
50 BHP
LX(L)-100 SG
LX Gas/Low NOx Series – Low and High Pressure Steam Boiler
100 BHP
LX-150 SG
LX Gas/Low NOx Series – Low and High Pressure Steam Boiler
150 BHP
LX(L)-200 SG
LX Gas/Low NOx Series – Low and High Pressure Steam Boiler
200 BHP
LX Gas/Low NOx Series – Low and High Pressure Steam Boiler
300 BHP
LX-300 Combustion Poster
LX-300 Water Poster
LX-300 Old vs New Side-by-side Comparison
LX Series Comparison Chart
  LX-50 LX-100 LX-150 LX-200 LX-300 [7]
Utilization Horsepower [1] 50HP 100HP 150HP 200HP 300HP
Maximum Pressure 170 PSIG MAWP, 150 PSIG Maximum Operating (15 PSIG MAWP)
Equivalent Output [2] 1,725 LB/HR 3,450 LB/HR 5,175 LB/HR 6,900 LB/HR 10,350 LB/HR
Heat Output 1,674,000 BTU/HR 3,348,000 BTU/HR 5,022,000 BTU/HR 6,695,000 BTU/HR 10,050,000 BTU/HR
Efficiency (fuel to steam) [3] 85% (80% without Economizer) 87%
Heating Surface Area 192.4 FT² 269.0 FT² 388.2 FT² 387.7 FT² 611 FT²
Operational Weight 3,710 LBS 6,070 LBS 8,620 LBS 8,620 LBS 10,940 LBS
Shipping Weight 4,140 LBS 5,930 LBS 7,920 LBS 7,950 LBS 11,050 LBS
Width 40 in. (50 in.) 38 in. (50 in.) 43 in. (65 in.) 43 in. (65 in.) 63 in.
Length 96 in. (119 in.) 124 (155 in.) 139 in. (142 in.) 139 in. (142 in.) 153
Height 103 in. (147 in.) 111 in. (161 in.) 126 in. (131 in.) 126 in. (131 in.) 127
Combustion System Proprietary Forced Draft, Step Fired Modulation Hi-Low-Off 4 Position Step Burner (Hi-Low-Ignition-Off)
Ignition System Electric Spark Ignited, Interrupted Gas Pilot
Power Supply 208, 230, 460, 575V, 3 phase, 60Hz
Max. Electrical Consumption 6.5 KVA (5.0 KVA) 13.3 KVA (10.9 KVA) 22.1 KVA 24.3 KVA (19.0 KVA) refer to installation manual 1.8
Fuel Type [4] Natural Gas or Propane (3-5 PSIG)
Gas Consumption [5] 1,960 SCFH 3,920 SCFH 5,880 SCFH 7,850 SCFH 11,500 SCFH
Gas Supply Pressure 3-5 PSIG Natural Gas or Propane
Main Steam Outlet Valve 2 in. (4 in.) 2 in. (6 in.) 3 in. (8 in.) 3 in. (8 in.) 4 in.
Safety Valve Outlet [6] One 1 1/2 in. One 2 in. One 2 1/2 in. One 2 1/2 in. Two 2 1/2 in.
Main Water Inlet 3/4 in. 1 in. 1 in. 1 in. 1 1/2 in.
Fuel Gas Inlet 1 1/2 in. 2 in. 2 in. 2 in. 2 1/2 in.
Automatic Surface Blowdown One 3/8 in. Two 3/8 in.
Manual Blowdown Two 1 in. One 1 in. & One 1 1/4 in.
Chimney Diameter (ID) 12 in. 12 in. 20 in. 20 in. 20 in.
Flame Detector Ultraviolet Flame Eye Sensor
Pressure Control Adjustable Pressure Transducer and Switch
Liquid Volume Control Electric Conductivity Type
Overheat Protection Low Water Cut Off & Thermocouple
Notes
  1. Available 49 and 199 BHP rating for L.A. area.
  2. Equivalent output calculated from and at 212°F (100°C) feed water at 212°F (100°C) steam.
  3. Thermal efficiencies are based on high heating values of fuels at 68°F (20°C) feed water.
  4. UL and c-UL approved for natural gas or propane.
  5. Gas consumption based on natural gas with high heating 1004 BTU/SCF.
  6. Safety valve outlet size may change depending on the pressure setting.
  7. See Miura’s MI System brochure for more on how the new LX-300 zero-side-clearance layout offers the highest system capacity per square foot in the industry.

All Miura steam boilers are fully packaged and test fired at factory. Built to meet or exceed UL and ASME standards in U.S.A.; c-UL and B-51 standards in Canada. Low pressure steam is available in 50, 100 and 200HP only. California Low NOx option available