The most common cause of overheating and failure of boiler tubes is when hard scale forms on the boiler tube surfaces. This scale comes from calcium and magnesium in the water. But overheating and eventual failure of the boiler tubes isn’t the only side effect. Efficiency is also decreased in the short-term because of the scale's insulating effect on the heat transfer surfaces. A layer of scale just 1/8 inch thick can cause as much as 20-25% loss in efficiency - heat lost right up the boiler stack.
Miura's new MW regeneration process is designed to deliver a more consistent, highly softened water supply, with the added reliability of double tank alternation, our system integrated Colormetry hardness detector, and a control panel that interfaces with Miura's MOM and ER dashboard systems. Miura Water Softener and Hardness Detection can keep your boiler running smoothly and efficiently.
Miura's new MW regeneration process is designed to deliver a more consistent, highly softened water supply, with the added reliability of double tank alternation, our system integrated Colormetry hardness detector, and a control panel that interfaces with Miura's MOM and ER dashboard systems. Miura Water Softener and Hardness Detection can keep your boiler running smoothly and efficiently.
MW-150U
1300 GPH
MW-250U
2000 GPH
MW-400U
2600 GPH
MW-600U
4750 GPH
MW-1000U
7820 GPH
MW Series Comparison Chart
MW-150U | MW-250U | MW-400U | MW-600U | MW-1000U | ||
---|---|---|---|---|---|---|
Resin volume | 5.3 x 2 CFT | 8.8 x 2 CFT | 14.1 x 2 CFT | 21.2 x 2 CFT | 35.3 x 2 CFT | |
Standard flow rate | 1,300 GPH | 2,000 GPH | 2,600 GPH | 4,750 GPH | 7,920 GPH | |
Pressure loss (at normal operation) | 10 PSI | 17 PSI | 28 PSI | 10.2 PSI | 17.4 PSI | |
Required salt per regeneration | 29.8-79.4 LBS | 49.6-132.2 LBS | 79.4-211.6 LBS | 120-318 LBS | 199-530 LBS | |
Hardness removal capacity per generation (x1000 grain CaCO3) | 82-120 | 136-199 | 214-315 | 670-1096 | 1038-1641 | |
Maximum salt storage weight | 353 LBS | 529 LBS | 860 LBS | 1100 LBS | 1830 LBS | |
Raw water temperature range | 39-104°F | |||||
Raw water pressure range | 22-71 PSI | 22-71 PSI | 22-71 PSI | 26-71 PSI | 26-71 PSI | |
Regeneration drain | Drain per regeneration | 260-480 GAL | 480-565 GAL | 770-1000 GAL | 1290-1695 GAL | 2165-3015 GAL |
Peak flow | 4.6-8.7 GPM | 12.8-14.5 GPM | 17.8-23.6 GPM | 40-55 GPM | 54-87 GPM | |
Power supply | 100–220 VAC, 50/60 Hz, single-phase | |||||
Rated power consumption | 22 W | 22 W | 22 W | 42 W | 42 W | |
Electric capacity | 22 VA | 22 VA | 22 VA | 42 VA | 42 VA | |
Connection diameter | Inlet/outlet port | 1 1/2" (Internal thread: accessory piping) | 2-1/2” CLASS150 PVC FLANGE | 3” CLASS150 PVC FLANGE | ||
Drain port | 1" (External thread: control valve) | 2” CLASS150 PVC FLANGE | ||||
Dry weight | Water softener unit | 474 LBS | 838 LBS | 1323 LBS | 1875 LBS | 3021 LBS |
Brine tank | 33 LBS | 44 LBS | 77 LBS | 155 LBS | 199 LBS | |
Operational weight | Water softener unit | 872 LBS | 1466 LBS | 2183 LBS | 3264 LBS | 5800 LBS |
Brine tank | 882 LBS | 1213 LBS | 2205 LBS | 2757 LBS | 4477 LBS |